CV. Metrotama Modern

sql
FN-CTM CITY TIE MODULE
Hover to Zoom

28 May 2020
1 1
CALL

Specification of

 

Standard Feature

• Interfaces Fire Alarm Control Panels to a Local Energy type City Tie monitoring circuit

• Integrates Fire Alarm Control Panel EOL device into module for supervision of interface wiring

• Wide operating voltage

• Power limited operation

• Transient protection

• Terminals accept up to 14 AWG wire

• Mounts to a standard 4" electrical back box

SPECIFICATIONS

Operating Voltage 12 ~ 30 VDC

Average Current Consumption 0mA (Standby)

Alarm Current 1A for 0.5 seconds

Ambient Temperature 32°F (0 C) ~ 120°F (49C)

Maximum Humidity 90% RH, non-condensing

Dimensions 4.2"W X 4.7"H X 1.1"D

Weight Approximately 3.0 ounces

Mounting 4" square electrical box

DESCRIPTION

The FN-CTM City Tie Module is used to connect a Fire Alarm Control Panel to a Local Energy type City Tie Monitoring circuit. The FN-CTM City Tie Module circuit provides the power necessary to trip the Master Box Trip Coil when the Fire Alarm Control Panel goes into alarm. The City Tie Circuit is capable of providing 1A for 0.5 seconds to operate the Master Box Trip Coil. The wiring is supervised to the Master Box by placing the Fire Alarm Control Panel EOL device on the terminals of the FN-CTM City Tie Module.