Specification of Fire Alarm DCP AMS SERIES ADDRESSABLE MANUAL PULL STATIONS
Fire Alarm
DCP-AMS SERIES
ADDRESSABLE MANUAL PULL STATIONS
HOCHIKI
STANDARD FEATURES
• Addressable integrated design
• All metal construction
• Single and dual action models available
• Extremely easy to operate
• Bi-colored status LED indicates Standby and
Alarm conditions
• Address is programmable in EEPROM
• Address can be programmed when installed
• Key lock or hex key lock models available
• Enclosed switch with glass rod (included)
• Terminals accept up to 14AWG wire
• Surface mount back box available
• ADA compliant (except LP models)
SPECIFICATIONS
Operating Voltage (SLC) 17~41 VDC
Average Current Consumption 550uA (Typical)
660uA (Alarm)
Ambient Temperature 32°F (0 °C) ~ 120°F (49°C)
Maximum Humidity 90% RH, non-condensing
Dimensions 3.4"W x 4.8"H x 2.0"D
Mounting Single gang or 4" square
electrical box
MODEL DESCRIPTION
DCP-AMS Single Action Hex Key Lock
DCP-AMS-LP Dual Action Hex Key Lock
DCP-AMS-KL Single Action Key Lock
DCP-AMS-KL-LP Dual Action Key Lock
DESCRIPTION
The DCP-AMS are the Hochiki America series of
addressable manual pull stations that provide a fast and
practical means of manually initiating a fire alarm signal.
Both single action and dual action manual pull stations
are available. Resetting of the pull station requires either
a Cat 30 key or a 1/8" hex key (depending upon the
model used).
An alarm condition is actuated by pulling down on the
handle of the DCP-AMS and DCP-AMS-KL single action
models. On the dual action models DCP-AMS-LP and
DCP-AMS-KL-LP the Lift and Pull cover must be lifted
before pulling down on the pull station handle. Once
the pull station is activated, the handle cannot be put
back into a normal standby condition without using the
key operated reset feature.
The DCP-AMS series is electronically addressable and
includes a bi-colored status LED. The LED blinks green
indicating normal communication with the DCP
compatible SLC loop. When an alarm condition is
actuated by pulling the handle, the LED will latch Red
to indicate the alarm condition.