sql

HES24 & HEC24 Series Evacuation Signals

CALL
Last Updated
05 Jul 2024
Minimum Order
1 1
Category
HOCHIKI

Fire Suppression System


STANDARD FEATURES




  • Nominal voltage 24VDC




  • Fixed candela option of 15/75 and 177




  • Unit Dimensions: 5" high x 4.5" wide x 2.5" deep




  • Synchronize strobe and/or horn with Hochiki Series Control Module




  • Prewire entire system, then install signals




  • Lower installation and operating costs




  • Input terminals supports 12 to 18 gauge wire




  • Switch selection for high or low dBA




  • Switch for chime, whoop, mechanical and 2400Hz tone

  • Switch for continuous or temporal 3 (not available on whoop tone)




  • Surface mount with the HSB (Hochiki surface mount box)




  • Silence horn while strobes remain flashing




  • Tamperproof re-entrant grill




  • Faceplate available in red or off-white



APPLICATIONS



The HES24 & HEC24 Series is a low profile strobe and horn/strobe combination that offers dependable audible and visual alarms and the lowest current available.



The HES24 & HEC24 Series is available in fixed candela options of 15/75 and 177.



The HES24 & HEC24 Series has a minimal operation current and has a minimum flash rate of 1Hz regard-less of input voltage.



The HES24 & HEC24 Series is shipped with the standard 4" metal mounting plate which incorporates the popular Slide feature that allows the installer to easily test for supervision. The product also features a locking mechanism which secures the product to the bracket without any screws showing.



The HES24 & HEC24 Series appliances are UL 464 and UL 1971 listed for use with fire protective systems and are warranted for three years from date of pur-chase.


HES24 24VDC Low Profile Evacuation Strobe























































Model



Part



Nominal



Candela



Number



Number



Voltage





HES24-177WR



0500-05760



24 VDC



177



HES24-177WW



0500-05770



24 VDC



177



HES24-1575WR



0500-05740



24 VDC



15 (UL 1971) /









75 (UL 1638)



HES24-1575WW



0500-05750



24 VDC



15 (UL 1971) /









75 (UL 1638)




HEC24 Fixed Candela Low Profile Evacuation Horn/Strobe







































































































Model



Part



Nominal



Candela



Reverberant dba @



In Anechoic Room



Number



Number



Voltage





10ft., per UL 464



dBA @ 10ft.



HEC24-177WR



0500-05840



24 VDC



177



70-82



100



HEC24-177WW



0500-05850



24 VDC



177



70-82



100



HEC24-1575WR



0500-05800



24 VDC



15 (UL 1971)



70-82



100









75 (UL 1638)







HEC24-1575WW



0500-05810



24 VDC



15 (UL 1971)



70-82



100









75 (UL 1638)







HEC24-1575PWR



0500-05820



24 VDC



15 (UL 1971)



70-82



100









75 (UL 1638)







HEC24-1575PWW



0500-05830



24 VDC



15 (UL 1971)



70-82



100









75 (UL 1638)








HES-24 & HEC-24 Product Strobe Current Ratings




























24VDC (16-33 Volts)



Candela



24VDC



UL Max



15/75



63mA



67mA



177



96mA



213mA




HES-24 & HEC-24 Product Horn Current Ratings



































































Horn Mode



Minimum dBA



Minimum dBA



Regulated 24VDC





@ 10ft., per



@ 10ft., per



Max. Operating @





UL 464 (HIGH)



UL 464 (LOW)



High Setting (mA)



Temp 3 2400Hz



78



71*



28



Temp 3 Mechanical



76



70*



25



Temp 3 Chime



70*



66*



15



Continuous 2400Hz



81



74*



28



Continuous Mechanical



80



72*



25



Continuous Chime



70*



66*



15



Whoop



82



69*



56