Specification of Marine Approved Analogue Addressable Manual Call Point with Short-Circuit Isolator
Model HCP-EM(SCI) is a Manual Call Point with integral short-circuit isolator, which is fully compatible with Hochiki’s ESP analogue addressable protocol. The unit
incorporates a bi-coloured LED, which can be selected as pulsing/non-pulsing*1 for communications polling and is continuously lit when the unit is operated – in
these two states the LED will show red. The LED will show amber when a short-circuit is present but will switch to red if the unit is activated. The unit operates by
pressing the EN54 compliant non-frangible (plastic) element and produces a high level ESP interrupt. A built in test function initiated by the control panel ensures
the integrity of the device at all times and the device can be tested by insertion of a test key in the underside of the unit. Two terminal blocks are provided for easy
connection to the loop wiring.
The unit is addressed using the TCH-B200 Hand Held Programmer for quick and reliable addressing. The unit can be flush mounted as supplied. For surface fixing a
suitable back box such as the SR MOUNTING BOX is required (sold separately). An optional glass element is also available